Item request has been placed! ×
Item request cannot be made. ×
loading  Processing Request

Detection of ferroresonance occurrence in inductive voltage transformers through vibration analysis

Item request has been placed! ×
Item request cannot be made. ×
loading   Processing Request
  • Additional Information
    • Contributors:
      Universidad de Cantabria
    • Publication Information:
      Elsevier
    • Publication Date:
      2019
    • Collection:
      Universidad de Cantabria: UCrea
    • Abstract:
      Steady state ferroresonances in isolated neutral electrical systems result in sustained abnormal system oscillations, which can damage inductive voltage transformers (IVTs) and other system elements. During this phenomenon, the IVT becomes saturated; consequently, the dimensions of the ferromagnetic material of the IVT change owing to magnetostriction. Because of this inherently nonlinear behaviour, the natural vibration modes of the IVT are excited. The aim of this study is to take advantage of these anomalous vibration modes to reveal the occurrence of ferroresonance in IVTs. The methodology for ferroresonance detection in IVTs through vibration analysis is described and demonstrated experimentally. ; This work was supported by the Spanish government under RETOS RTC-2015-4176-3, Innovation in the automation of the isolated neutral distribution.
    • Relation:
      https://doi.org/10.1016/j.ijepes.2018.10.011; info:eu-repo/grantAgreement/MINECO//RTC-2015-3795-3Q3918001CCANTABRIA/ES/SPADI: Sistema predictivo de ampacidad dinámica en líneas aero-subterráneas/; https://hdl.handle.net/10902/35080
    • Accession Number:
      10.1016/j.ijepes.2018.10.011
    • Online Access:
      https://hdl.handle.net/10902/35080
      https://doi.org/10.1016/j.ijepes.2018.10.011
    • Rights:
      © 2018. This manuscript version is made available under the CC-BY-NC-ND 4.0 license ; http://creativecommons.org/licenses/by-nc-nd/4.0/ ; openAccess
    • Accession Number:
      edsbas.AE9BD48B